Skip to main content
Siemens 5SL6263-6 — 2-Pole MCB (DIN Rail)

Siemens 5SL6263-6 SENTRON MCB, 2P B 63A 6kA

MPN5SL6263-6
Active

Siemens SENTRON 5SL6263-6, 2-pole miniature circuit breaker, B tripping characteristic, 63 A rated current at 30 °C, 6 kA breaking capacity (EN 60898), 400 V AC, width 36 mm (2 MW).

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6263-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Application environmentResidential buildings/infrastructure
5SL6263-6 — Electrical
ParameterValue
Number of poles2
5SL6263-6 — Protection
ParameterValue
Tripping characteristic classB
Overvoltage categoryIII
5SL6263-6 — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL6263-6 — Environmental
ParameterValue
Pollution degree2
5SL6263-6 — Specifications
ParameterValue
Energy Limitation Class3

Product details

Integrator's note — 5SL6263-6

The Siemens 5SL6263-6 is a 2-pole miniature circuit breaker from the SENTRON range, B-curve, rated 63 A at 30 °C per EN 60898 and IEC 60947-2. Derate to 59.18 A at 40 °C and 52.93 A at 55 °C if the panel ambient runs warm.

Panel fit & environment

Overvoltage category III, pollution degree 2. Sealable, halogen-free, silicon-free. Mechanical service life typical 10 000 operating cycles.

Frequently asked questions

Where can I buy 5SL6263-6 and get a price?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

What is the breaking capacity of 5SL6263-6?

6 kA per both EN 60898 and IEC 60947-2.

Will 5SL6263-6 drop into a panel specified around 5SL4120-7CC?

Both are 2-pole SENTRON MCBs on the same 36 mm footprint, so mechanical fit is identical. The 5SL6263-6 is a B-curve 63 A unit; the 5SL4120-7CC is a different rating and curve — verify the branch circuit requirements before substituting.

MPN
5SL6263-6