Siemens 5SL6302-7CC — 3-Pole MCB (DIN Rail)

Siemens 5SL6302-7CC SENTRON MCB, 3P C 2A 6kA 400V

MPN5SL6302-7CC
Active

Siemens SENTRON 5SL6302-7CC miniature circuit breaker, 3-pole, C-curve, 2 A rated, 6 kA breaking capacity per EN 60898 at 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6302-7CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL6302-7CC — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL6302-7CC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.3 W
5SL6302-7CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL6302-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)50 m/s² at 25 to 150 Hz

Product details

The Siemens 5SL6302-7CC is a SENTRON miniature circuit breaker (MCB) — 3-pole, C-curve, rated 2 A, with a 6 kA breaking capacity per EN 60898 at 400 V AC.

Mounting position is unrestricted — vertical, horizontal, upside-down, all fine. The IP20 rating (with conductors connected) is standard for enclosed distribution boards; it's not a standalone outdoor part. Sealable, halogen-free, silicon-free — relevant for panels in sensitive environments like hospitals or labs where outgassing matters.

The 5SL4363-7 is dimensionally identical (same 76 mm depth, 54 mm width, 90 mm height, same 3-pole C-curve footprint) and shares the same 400 V AC rated voltage, same temperature range, same IP20 rating. The critical difference: the 5SL4363-7 carries a 10 kA breaking capacity per both EN 60898 and IEC 60947-2, versus this part's 6 kA. If your panel's prospective short-circuit current (PSCC) at the board exceeds 6 kA, you need the 5SL4363-7. If it's 6 kA or below, this part drops in without rewiring — same rail, same busbar pitch, same termination.

Frequently asked questions

Where can I buy 5SL6302-7CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of 5SL6302-7CC?

6 kA per EN 60898 at 400 V AC. That's the standard rating for residential and light commercial distribution boards.

Will 5SL6302-7CC fit in a panel designed for 5SL4363-7?

Yes — same 76 mm depth, 54 mm width, 90 mm height, same 3-pole C-curve footprint, same DIN-rail mounting. The only difference is breaking capacity: 6 kA vs 10 kA. If your fault level is 6 kA or below, it's a direct swap.

What is the operating temperature range?

-40 °C to +75 °C, which covers most indoor and outdoor enclosed panel environments.