Skip to main content
Siemens 5SL6302-7MB — 3-Pole MCB (DIN Rail)

Siemens 5SL6302-7MB SENTRON MCB, 3P C 2A 6kA 400V

MPN5SL6302-7MB
Active

Siemens SENTRON 5SL6302-7MB miniature circuit breaker, 3-pole, C-curve, 2 A rated current, 6 kA breaking capacity at 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6302-7MB — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL6302-7MB — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL6302-7MB — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.25 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)250 V
5SL6302-7MB — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL6302-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)no

Product details

What this MCB is and what the ratings mean

The Siemens 5SL6302-7MB is a SENTRON miniature circuit breaker — a 3-pole, C-curve unit rated 2 A with a 6 kA breaking capacity per EN 60898 at 400 V AC. The C-curve means it trips between 5 and 10 times rated current, so it handles moderate inrush from small motor loads or transformer banks without nuisance tripping, while still clearing a hard short fast enough to protect the downstream cable. The 6 kA rating at 400 V tells you the maximum prospective fault current it can safely interrupt; for residential and light commercial distribution boards where the supply transformer limits fault current to that level, this MCB is sized correctly. It occupies 3 modular width units (54 mm) on a DIN rail, with an installation depth of 70 mm behind the panel face.

Physical fit and panel integration

Snaps onto standard 35 mm DIN rail in any mounting position. The 54 mm width (3 MW) and 76 mm depth leave enough clearance for adjacent breakers and busbar feeders in a typical SENTRON distribution board. IP20 with connected conductors — fine inside a closed panel, not for wet environments. Sealable design allows the installer to lock the toggle position after commissioning, which keeps unauthorized hands off a critical lighting or safety circuit.

Environmental and compliance notes

Halogen-free and silicon-free construction — relevant for semiconductor fabs or clean-room panels where outgassing contaminates processes. Rated for ambient temperatures from -40 °C to +75 °C, so it holds calibration in unheated electrical rooms or outdoor enclosures. Pollution degree 2 and overvoltage category III, which is standard for fixed-installation distribution boards.

Frequently asked questions

Where can I buy 5SL6302-7MB and how is it quoted?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the closest functional alternative to 5SL6302-7MB?

The 5SL4363-7 is a near-identical sibling in the same SENTRON family: same 3-pole, C-curve, 400 V AC rating, same 76×54×90 mm footprint and 3 MW width. The key difference is breaking capacity — 5SL4363-7 is rated 10 kA per EN 60898 and IEC 60947-2, versus 6 kA for the 5SL6302-7MB. If your panel's prospective fault current exceeds 6 kA, the 5SL4363-7 is the drop-in upgrade without rewiring.

Will 5SL6302-7MB drop into a panel specified for 5SL4363-7?

Yes, the two share the same physical dimensions (76 mm depth, 54 mm width, 90 mm height), same 3 MW DIN-rail footprint, same mounting position flexibility, and same terminal layout. No rewiring or busbar modification is needed.

MPN
5SL6302-7MB