SENTRON 5SL6306-6CC — 3-pole B-curve MCB for branch-circuit protection
At 30 °C the breaker carries its full 6 A; at 40 °C derate to 5.66 A, at 50 °C to 5.29 A, and at 55 °C to 5.1 A — a thermal derating curve that matters when packing multiple units into a closed panel. Rated impulse withstand voltage corresponds to overvoltage category III, pollution degree 2 — the standard for fixed-installation distribution boards downstream of the main switchgear.
Integration — DIN-rail footprint and panel fit
At 54 mm wide (3 MW), 90 mm high, and 76 mm deep with an installation depth of 70 mm, the 5SL6306-6CC fits standard SENTRON distribution boards and enclosure cutouts. Sealable design allows tamper-proof locking of the toggle position for safety-isolation points.
Designed to EN 60898 for breaking capacity at 6 kA and to IEC 60947-2 for the overvoltage category III / pollution degree 2 rating. The product designation per EN 61346-2 and IEC 81346-2 is F (protective device). Vibration resistance tested to IEC 60068-2-6 at 50 m/s² from 25 to 150 Hz.