Skip to main content
Siemens 5SL6316-7BB — Miniature Circuit Breakers (MCB)

Siemens SENTRON 5SL6316-7BB MCB, 3P C-16A, 6kA, 400V

MPN5SL6316-7BB

Siemens SENTRON miniature circuit breaker, 3-pole, C-curve, 16 A, 400 V AC, 6 kA per EN 60898, 3 MW units, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6316-7BB — Ratings
ParameterValue
Overvoltage categoryIII
5SL6316-7BB — Mechanical
ParameterValue
Width54 mm
Height90 mm
Depth76 mm

Product details

The Siemens SENTRON 5SL6316-7BB is a 3-pole miniature circuit breaker rated 16 A with a C tripping characteristic, designed for 400 V AC multi-phase operation at 50/60 Hz. Its breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, which means it safely interrupts short-circuit faults up to 6 kA without upstream device coordination issues in residential and infrastructure panels.

Occupying 3 modular width units (54 mm) on a DIN rail, the breaker mounts in any position with an installation depth of 70 mm and overall depth of 76 mm. The IP20 rating applies with connected conductors, so the front face is touch-safe once wired; no additional finger-duct cover is required for standard panel builds.

Frequently asked questions

Where can I buy 5SL6316-7BB and get a price?

This part is sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial response.

Will 5SL6316-7BB drop into a panel specified for 5SL4363-7 without rewiring?

Yes, the two breakers share identical dimensions (76 mm depth, 54 mm width, 90 mm height), mounting position flexibility, and the same 3-pole C-curve footprint. The key difference is breaking capacity: 5SL4363-7 is rated 10 kA versus 6 kA for this unit. If the panel's fault level is below 6 kA, the swap is mechanical and electrical drop-in.

What compliance documentation does Siemens provide for 5SL6316-7BB?

The breaker carries IEC/EN 60898-1 and IEC 60947-2 ratings, is halogen-free and silicon-free, and is designed for overvoltage category III / pollution degree 2. Standard Siemens declarations of conformity (CE, UKCA) and material compliance (RoHS, REACH) are available on request.

MPN