Siemens 5SL6316-7MB — 3-Pole MCB (DIN Rail)

Siemens 5SL6316-7MB SENTRON MCB, 3P C 16A 6kA, 400V

MPN5SL6316-7MB
Active

Siemens SENTRON 5SL6316-7MB miniature circuit breaker, 3-pole, C-curve, 16 A, 6 kA breaking capacity per EN 60898 at 400 V AC, 3 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6316-7MB — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL6316-7MB — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2
5SL6316-7MB — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)1.7 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)250 V
5SL6316-7MB — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL6316-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6316-7MB is a SENTRON miniature circuit breaker (MCB) rated 16 A with a C tripping characteristic, 3 poles, and a 6 kA breaking capacity per EN 60898 at 400 V AC.

The closest functional peer within the SENTRON 5SL6 family is the 5SL4363-7 — same 3-pole, C-curve, 400 V AC rating, same dimensions (76 mm depth, 54 mm width, 90 mm height), same IP20 with connected conductors, and same mechanical service life of 10 000 operating cycles. The key difference: the 5SL4363-7 carries a 10 kA breaking capacity per both EN 60898 and IEC 60947-2, versus the 6 kA of the 5SL6316-7MB. If the panel's available fault current at the distribution board exceeds 6 kA, the 5SL4363-7 is the drop-in replacement — same footprint, same wiring, no rewiring needed.

Frequently asked questions

What is the breaking capacity of the 5SL6316-7MB?

The 5SL6316-7MB has a 6 kA breaking capacity according to EN 60898 at 400 V AC. This is the maximum fault current it can safely interrupt at that voltage.

Will the 5SL6316-7MB drop into a panel specified for the 5SL4363-7?

Yes, the 5SL6316-7MB shares the same dimensions (76 mm depth, 54 mm width, 90 mm height) and mounting as the 5SL4363-7. The only difference is the breaking capacity — 6 kA versus 10 kA. If the available fault current is 6 kA or less, it is a direct mechanical and electrical swap.

Where can I buy the 5SL6316-7MB and get current pricing?

The 5SL6316-7MB is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote — submit an RFQ for a firm price and lead time.

MPN
5SL6316-7MB