Siemens 5SL6325-7MB — 3-Pole MCB (DIN Rail)

Siemens 5SL6325-7MB SENTRON MCB, 3P C-curve 25A, 6kA

MPN5SL6325-7MB
Active

Siemens SENTRON 5SL6325-7MB miniature circuit breaker, 3-pole, C-curve, 25 A, 6 kA interrupting capacity per EN 60898, 400 V AC, 3 modular width units.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsListing updated Jul 2026

Specifications

Identification

5SL6325-7MB — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure

Protection

5SL6325-7MB — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608986 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation class3
Pollution degree2

Electrical

5SL6325-7MB — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)2.2 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)250 V

Mechanical

5SL6325-7MB — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes

Environmental

5SL6325-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

Siemens 5SL6325-7MB SENTRON MCB — 3-pole, C-curve, 25 A, 6 kA

The Siemens 5SL6325-7MB is a 3-pole miniature circuit breaker from the SENTRON family, rated 25 A with a C-curve trip characteristic. It breaks fault currents up to 6 kA per EN 60898 at 400 V AC — the standard interrupting rating for residential and light commercial distribution boards in 50/60 Hz networks. The C-curve means it trips between 5× and 10× rated current, so it handles moderate inrush from motorized loads like pumps or compressors without nuisance tripping, while still clearing short-circuit faults fast enough to protect downstream wiring.

Panel fit and integration

The 5SL6325-7MB occupies 3 modular width units (54 mm) on a DIN rail, with a depth of 76 mm and an installation depth of 70 mm. It mounts in any position, accepts supplementary devices (auxiliary contacts, shunt trips, alarm switches), and is sealable — useful for panel builders who need to lock settings after commissioning. The IP20 rating applies only with connected conductors, so the busbar area stays live; standard for distribution board use.

Frequently asked questions

How do I get current pricing and availability for 5SL6325-7MB?

Submit an RFQ through this listing. Availability and current pricing are confirmed at quote time through independent distribution channels.

Will 5SL6325-7MB drop into a panel specified around 5SL4363-7 without rewiring?

Yes — both share the same 3-pole, 3-module-width (54 mm) footprint, same 76 mm depth, same 70 mm installation depth, and same DIN-rail mounting. The 5SL4363-7 carries a 10 kA interrupting rating (EN 60898) versus the 5SL6325-7MB's 6 kA, but the physical fit and terminal layout are identical, so a direct swap is possible if the available fault current at the panel does not exceed 6 kA.

What compliance documentation does this brand provide for 5SL6325-7MB?

Siemens SENTRON 5SL series MCBs carry CE marking per the Low Voltage Directive. The part is halogen-free and silicon-free. Standard documentation includes the declaration of conformity and the product datasheet.

MPN