Skip to main content
Siemens 5SL6332-8CC — 3-Pole MCB (DIN Rail)

Siemens 5SL6332-8CC SENTRON MCB, 3P D 32A 6kA

MPN5SL6332-8CC
Active

Siemens SENTRON 5SL6332-8CC, miniature circuit breaker, 3-pole, D tripping characteristic, 32 A rated, 6 kA breaking capacity per EN 60898 at 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6332-8CC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL6332-8CC — Protection
ParameterValue
Tripping characteristic (curve)D
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Pollution degree2
5SL6332-8CC — Electrical
ParameterValue
Rated current (AC)32 A
Rated voltage (AC, multi-phase)440 V
5SL6332-8CC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
5SL6332-8CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes

Product details

What the ratings mean for fit

The 5SL6332-8CC is a SENTRON miniature circuit breaker — 3-pole, D-curve, rated 32 A at 400 V AC with a 6 kA breaking capacity per EN 60898. The D characteristic means it tolerates high inrush currents (5–10× rated), so it's the right call for motor, transformer, or lighting ballast circuits where a B or C curve would nuisance-trip on startup. At 30 °C it carries the full 32 A; at 40 °C it derates to 30.18 A, at 50 °C to 28.24 A — so if your panel ambient runs hot, size the load accordingly or move up a frame. The 6 kA SCCR at 400 V covers most residential and light commercial service-entrance faults; if your available fault current is higher, you'll need a current-limiting upstream device.

Panel integration and mounting

Snaps onto DIN rail, any mounting position — no orientation restrictions. Occupies 3 modular width units (54 mm wide), with an installation depth of 70 mm and overall depth of 76 mm. The IP20 rating (with connected conductors) is standard for enclosed distribution boards; not for wet or washdown locations. Touch protection is built in, and the unit is sealable — useful for utility or metering applications where tamper evidence matters. Vibration resistance is rated at 50 m/s² over 25 to 150 Hz per IEC 60068-2-6, so it holds up on machine-mounted subpanels.

Environmental and compliance notes

Halogen-free and silicon-free construction — relevant for clean-room, semiconductor, or high-reliability installations where outgassing or contamination is a concern. Rated for pollution degree 2 and overvoltage category III, which covers fixed-installation distribution boards. Operating temperature range spans -40 °C to 75 °C, so it's fine in unheated enclosures or outdoor-rated cabinets as long as they stay dry. The product designation per EN 61346-2 and IEC 81346-2 is 'F' — that's the standard function code for circuit protection.

Frequently asked questions

What is the breaking capacity of 5SL6332-8CC?

6 kA per EN 60898 at 400 V AC. That's the rated short-circuit capacity for this miniature circuit breaker.

What does the D-curve mean on this MCB?

The D tripping characteristic allows magnetic trip at 5–10× rated current (32 A), so it handles high inrush loads like motors, transformers, and discharge lighting without nuisance tripping.

Where can I buy 5SL6332-8CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is published here.

What is the difference between 5SL6332-8CC and 5SL3340-7CC?

The 5SL6332-8CC is a 3-pole D-curve 32 A breaker; the 5SL3340-7CC is a different rating or curve variant in the same SENTRON family. The deciding factor is your load's inrush profile and ampacity — the D-curve suits motor/transformer circuits where a C-curve might trip on startup.

MPN
5SL6332-8CC