Skip to main content
Siemens 5SL6340-7RC — 3-Pole MCB (DIN Rail)

Siemens 5SL6340-7RC SENTRON MCB, 40 A, 3-Pole, C Curve, 7.5

MPN5SL6340-7RC
Active

Siemens SENTRON 5SL6340-7RC miniature circuit breaker, 40 A, 3-pole, C characteristic, 7.5 kA breaking capacity per EN 60898, 415/440 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6340-7RC — Identification
ParameterValue
Brand nameSENTRON
Number of poles3
Pole configuration3P
Suitability for operationResidential buildings/infrastructure
5SL6340-7RC — Protection
ParameterValue
Tripping characteristic (curve)C
Breaking capacity per EN 608987.5 kA
Overvoltage categoryIII
IP protection classIP20, with connected conductors
Energy limitation classNo
Pollution degree2
5SL6340-7RC — Electrical
ParameterValue
Rated voltage (AC, multi-phase)440 V
Voltage type (AC/DC)AC
Supply frequency range50/60 Hz
Power loss per pole at rated current (AC, hot)3.3 W
Mechanical service life (operating cycles, typ.)10 000
Rated voltage (AC, single-phase)250 V
5SL6340-7RC — Mechanical
ParameterValue
Modular width units3
Mounting positionany
Width54 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Terminal tightening torque, max.75 °C
Terminal tightening torque, min.-40 °C
SealableYes
Accepts supplementary devicesYes
5SL6340-7RC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Vibration resistance (IEC 60068-2-6)no

Product details

The Siemens SENTRON 5SL6340-7RC is a 40 A, 3-pole miniature circuit breaker with a C tripping characteristic and a 7.5 kA breaking capacity rated per EN 60898 at 415 V AC. It's designed for residential and infrastructure branch-circuit protection where moderate inrush currents — typical of lighting, small motor, and general-purpose loads — need a delayed magnetic trip to avoid nuisance tripping on startup.

The 5SL6340-7RC snaps onto a DIN rail and occupies 3 modular width units (54 mm total width), with a depth of 76 mm and an installation depth of 70 mm behind the panel face.

Rated for multi-phase operation up to 440 V AC and single-phase up to 250 V AC, with a frequency range of 50/60 Hz. The C curve trips magnetically between 5 and 10 times rated current, so a 40 A breaker clears faults roughly between 200 A and 400 A instantaneously — suitable for circuits where the inrush from motors or transformers would otherwise trip a B curve. Power loss is 3.3 W per pole in hot operating state at rated current, which adds about 10 W total heat dissipation inside the enclosure — factor that into your thermal budget for a multi-breaker panel.

The breaker accepts supplementary devices (shunt trips, auxiliary contacts, alarm switches) for remote signaling or emergency-off integration. The housing is sealable — a lockable cover or lead-seal wire can be fitted to prevent unauthorized switching, which is a common requirement in metering or safety-critical circuits.

Frequently asked questions

Will 5SL6340-7RC drop into a panel specified around 5SL4363-7 without rewiring?

Yes, the 5SL6340-7RC and 5SL4363-7 share identical dimensions (76 mm depth, 54 mm width, 90 mm height), mounting position (any), and DIN-rail footprint, so a direct swap is mechanically possible. The key difference is the breaking capacity: the 5SL4363-7 is rated 10 kA per EN 60898, while the 5SL6340-7RC is rated 7.5 kA — verify the fault-current study before substituting.

Where can I buy 5SL6340-7RC and how is it quoted?

The 5SL6340-7RC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the breaking capacity of 5SL6340-7RC?

The 5SL6340-7RC has a rated breaking capacity of 7.5 kA according to EN 60898 at 415 V AC, and is rated for multi-phase operation up to 440 V AC.

MPN
5SL6340-7RC