Siemens 5SL6350-7BB — 50 A C-Curve MCB, 3-Pole, 6 kA
At 40 °C ambient the 50 A rating derates to 47.36 A; at 55 °C it drops to 43.09 A, so the thermal curve matters if the panel runs hot.
Physical Integration
Mounting position is any orientation. The sealable design allows panel-lockout tagging for lockout/tagout procedures. Halogen-free and silicon-free construction reduces off-gassing risk in enclosed distribution boards.
Electrical Ratings & Coordination
The DC rating is limited to 72 V maximum. The unit accepts auxiliary switches, shunt trips, and other add-on devices for remote signaling or emergency-off circuits.