Temperature derating and real-world current
At 40 °C the breaker is rated 59.67 A, at 45 °C it drops to 57.96 A, and at 55 °C it's 54.29 A. If your panel runs warm — common in enclosed DIN-rail assemblies — size the load against the derated figure, not the 30 °C number. The 6 kA breaking capacity is the same under both IEC 60898 (household) and IEC 60947-2 (industrial) standards, so it qualifies for either classification without a coordination study change.
Snaps onto standard DIN rail, 3 modular-width units (54 mm wide). Sealable, halogen-free, silicon-free. Touch protection is built in.