The 5SL6402-7CC: The C-curve means it trips between 5 and 10 times rated current (10–20 A for this 2 A unit), making it suitable for general-purpose branch-circuit protection where moderate inrush from small motors or lighting ballasts is expected. This MCB is a 4-pole device (3 phases + neutral switched) in a single modular housing — standard DIN-rail mount, 4 modules wide. The neutral pole switches and protects, not just isolates, which matters for TN and TT systems where the neutral carries fault current.
Compliance and distribution
RoHS compliant since 01-06-13. Export control: AL N / ECCN N — no dual-use restrictions. Product class B (return restricted) — this is a Siemens distribution-control flag, not a technical limitation.