Siemens 5SL6413-6 — 4-Pole MCB (DIN Rail)

Siemens 5SL6413-6 SENTRON MCB, 4P 13A B-Curve 6kA

MPN5SL6413-6
Active

Siemens SENTRON 5SL6413-6, 4-pole miniature circuit breaker, 13 A, B characteristic, 6 kA breaking capacity, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6413-6 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL6413-6 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC13 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)72 V
Voltage typeAC
5SL6413-6 — Protection
ParameterValue
Tripping characteristic (trip curve)B
Rated breaking capacity (Icn), per EN 608986 kA
Rated breaking capacity, per IEC 60947-26 kA
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingNo
Touch protectionYes
5SL6413-6 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL6413-6 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity

Product details

The 4-pole (4P) variant switches all three phases and the neutral — no separate neutral pole needed.

Width is 72 mm — that's 4 modular-width units (4 MW) on the rail. Mounting position is any — doesn't care if the rail is vertical or horizontal. Terminal touch protection is included, and the breaker is sealable for tamper-proof installations. Halogen-free and silicon-free construction, so no corrosive off-gassing in a sealed enclosure near sensitive electronics.

Thermal derating and environment

Rated 13 A at 30 °C ambient. Derates to 12.37 A at 40 °C, 11.96 A at 45 °C, and 11.36 A at 55 °C. If your panel runs warm — say 45 °C inside a packed enclosure — plan for that 1 A drop.

Frequently asked questions

Where can I buy the 5SL6413-6?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will 5SL6413-6 drop into a panel specified around 5SL6132-6MB without rewiring?

Both are 4-pole SENTRON MCBs on the same DIN-rail footprint, so the mechanical swap is straightforward. The 5SL6413-6 is a 13 A B-curve; the 5SL6132-6MB is a different rating and characteristic, so check your load and selectivity before the swap.

What is the 5SL6413-6's breaking capacity?

6 kA per both EN 60898 and IEC 60947-2, covering most residential and light commercial fault levels.

What compliance documentation does Siemens provide for 5SL6413-6?

The breaker is halogen-free and silicon-free, rated for overvoltage category III and pollution degree 2. Standard Siemens SENTRON documentation includes RoHS and REACH declarations; specific certificates are available on request.