Skip to main content
Siemens 5SL6425-7 — 4-Pole MCB (DIN Rail)

Siemens 5SL6425-7 SENTRON MCB, 4P C 25A 6kA 400V

MPN5SL6425-7
Active

Siemens SENTRON 5SL6425-7, miniature circuit breaker, 4-pole, C characteristic, 25 A rated current, 6 kA breaking capacity at 400 V AC, 4 modular width units.

$19.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6425-7 — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL6425-7 — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated current (In), AC25 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)72 V
5SL6425-7 — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
Touch protectionYes
5SL6425-7 — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL6425-7 — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL6425-7 — Performance
ParameterValue
Mechanical service life (switching cycles, typ.)10 000

Product details

Siemens 5SL6425-7 SENTRON MCB — 4-pole, C-curve, 25 A, 6 kA

The Siemens 5SL6425-7 is a SENTRON miniature circuit breaker (MCB) rated 25 A at 400 V AC with a C tripping characteristic and a 6 kA breaking capacity certified to both EN 60898 and IEC 60947-2. The 4-pole (4P) design switches all three phases plus the neutral, though the neutral pole is not switched internally (no neutral conductor switching). Rated at 25 A at both 30 °C and 40 °C (23.79 A at 40 °C per the spec), the breaker derates to 23 A at 45 °C and 21.85 A at 55 °C — a consideration if the panel ambient runs hot.

Height is 90 mm. Halogen-free and silicon-free construction meets the material restrictions common in clean manufacturing environments.

The 5SL6425-7 carries the SENTRON brand designation. It is classified per EN 61346-2 and IEC 81346-2 as function F (protective device). Energy limitation class 3 indicates it limits let-through energy to a level that protects downstream equipment during a short-circuit event. Touch protection is provided on the terminals.

Frequently asked questions

What is the breaking capacity of the 5SL6425-7?

6 kA at 400 V AC, certified to both EN 60898 and IEC 60947-2. This covers typical commercial and light industrial fault levels.

What is the C-curve tripping characteristic?

The C characteristic trips between 5× and 10× rated current (125 A to 250 A for this 25 A breaker). It is the standard choice for general-purpose loads like motors, lighting, and socket outlets.

Where can I buy the 5SL6425-7?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm offer.

Does the 5SL6425-7 switch the neutral?

No. The neutral conductor is not switched internally (neutral conductor switching: No). The 4-pole design provides a through path for the neutral but does not open it.

MPN