Skip to main content
Siemens 5SL6425-7BB — Miniature Circuit Breakers (MCB)

Siemens 5SL6425-7BB SENTRON MCB, 4P C-Curve 25A 6kA

MPN5SL6425-7BB

Siemens SENTRON 5SL6425-7BB, 4-pole miniature circuit breaker, C tripping characteristic, 25 A rated at 400 V AC, 6 kA breaking capacity, 4 MW width.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6425-7BB — Ratings
ParameterValue
Overvoltage categoryIII
5SL6425-7BB — Mechanical
ParameterValue
Width72 mm
Height90 mm
Depth76 mm

Product details

The Siemens SENTRON 5SL6425-7BB is a 4-pole miniature circuit breaker (MCB) with a C-curve tripping characteristic, rated 25 A at 400 V AC and 50 Hz. The kit is complete: breaker, busbar stabs, and terminal screws are in the box.

Width is 72 mm (4 modular units), depth 76 mm, height 90 mm.

Thermal derating and service life

Rated 25 A at 30 °C ambient; derates to 23.68 A at 40 °C, 23 A at 45 °C, and 21.54 A at 55 °C. Operating range covers -40 °C to 75 °C.

Frequently asked questions

Where can I buy 5SL6425-7BB and what is the lead time?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What is the closest functional second-source to 5SL6425-7BB?

The 5SL6550-7BB is a 4-pole C-curve MCB in the same SENTRON family but rated 50 A instead of 25 A. It shares the same 6 kA breaking capacity, 400 V AC rating, and 4-MW width, so it drops into the same DIN-rail footprint without rewiring — but the higher amp rating means it will not clear an overload on a 25 A circuit. For a direct amp-for-amp swap, stay with the 5SL6425-7BB.

What are the key physical dimensions of 5SL6425-7BB?

Depth is 76 mm, width 72 mm (4 modular units), height 90 mm. Installation depth behind the panel face is 70 mm.

Will 5SL6425-7BB drop into a panel specified around 5SL6550-7BB without rewiring?

Yes — both are 4-pole C-curve MCBs in 72 mm wide bodies that mount on standard DIN rail. The 5SL6425-7BB is rated 25 A versus 50 A for the 5SL6550-7BB, so the busbar and downstream conductors must be sized for 25 A. If the panel was wired for 50 A, dropping in a 25 A breaker is safe but limits the circuit capacity.

What compliance documentation does Siemens provide for 5SL6425-7BB?

The part is designed to EN 60898 and IEC 60947-2 for breaking capacity. It is halogen-free and silicon-free. The manufacturer typically provides CE, UKCA, and EAC declarations on request through the standard documentation portal.

MPN