Rated voltage is 415 V AC for multi-phase operation, with a maximum of 440 V AC. Single-phase operation is rated at 250 V AC. The 50/60 Hz frequency range covers standard mains supplies. Power loss per pole is 2.4 W in hot operating state — at full load on all four poles, expect about 9.6 W total heat dissipation inside the enclosure, which matters for thermal derating in a crowded DIN-rail panel. The neutral pole is switched, not just solid — confirm your distribution system requires a switched neutral before specifying. DC rated voltage is 72 V maximum, so this is primarily an AC device.
Width is 72 mm, which corresponds to 4 modular width units (18 mm per unit) on a standard DIN rail. The device is sealable — a seal cap can be fitted over the toggle to prevent unauthorized operation, common in metering or common-area distribution boards.
What compliance documentation is available
The 5SL6432-6RC carries Siemens SENTRON brand documentation including CE declaration of conformity to the Low Voltage Directive, RoHS and REACH compliance statements, and IEC/EN 60898 test certificates. The datasheet provides the full mechanical and electrical endurance figures — 10,000 operating cycles typical mechanical service life.