Skip to main content
Siemens 5SL6501-6CC — 1-Pole MCB (DIN Rail)

Siemens 5SL6501-6CC SENTRON MCB, 1 A, B Curve, 1P+N, 6 kA

MPN5SL6501-6CC
Active

Siemens SENTRON miniature circuit breaker, 5SL6501-6CC, 1 A, B-curve, 1P+N, 6 kA breaking capacity per EN 60898, 230 V AC, 2-module width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6501-6CC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL6501-6CC — Electrical & Protection
ParameterValue
Tripping characteristic classB
Energy limitation class3
Overvoltage categoryIII
5SL6501-6CC — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6501-6CC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6501-6CC is a SENTRON miniature circuit breaker (MCB) rated 1 A with a B tripping characteristic, 1P+N pole design, and a 6 kA interrupting capacity per EN 60898 at 230 V AC. It occupies two modular-width units (36 mm) on the DIN rail, which is standard for a 1P+N MCB that switches both phase and neutral.

The 6 kA rated short-circuit capacity per EN 60898 is the standard domestic-grade breaking capacity — it's sized for the typical fault levels in residential and commercial sub-distribution boards. The B characteristic means magnetic trip at 3 to 5 times In (3 to 5 A), so it's a good fit for cable protection and general-purpose loads that don't draw a heavy starting surge. The 1P+N design switches both the phase conductor and the neutral, which is required by some national wiring regulations for final circuits. The neutral pole is not overcurrent-protected — it's a switched neutral, not a protected pole. The MCB is sealable (padlockable in the OFF position) for lockout/tagout.

Frequently asked questions

What is the breaking capacity of 5SL6501-6CC?

The 5SL6501-6CC has a rated short-circuit capacity of 6 kA per EN 60898 at 230 V AC. This is the standard domestic-grade breaking capacity for residential and commercial sub-distribution boards.

What does the B curve mean on this MCB?

The B tripping characteristic means the magnetic trip operates at 3 to 5 times rated current (3 to 5 A for this 1 A unit). It's designed for cable protection and resistive loads that don't draw high inrush currents.

Will 5SL6501-6CC drop into a panel specified around 5SL6120-7?

No — the 5SL6501-6CC is 36 mm wide (2 modular units) for its 1P+N design, while the 5SL6120-7 is 18 mm wide (1 modular unit) for a 1P design. The 5SL6501-6CC also switches the neutral, so the wiring differs. They are not footprint-compatible without rewiring and re-spacing on the DIN rail.

Where can I buy 5SL6501-6CC?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
5SL6501-6CC