Siemens 5SL6502-7 — 1-Pole MCB (DIN Rail)

Siemens 5SL6502-7 SENTRON MCB, 2A C-Curve, 1P+N, 6kA

MPN5SL6502-7
Active

Siemens SENTRON miniature circuit breaker, 5SL6502-7, 1P+N, C-curve 2A, 230 V AC, 6 kA per EN 60898, 2 MW units, IP20.

$9.91Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6502-7 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Pole design1P+N
Application suitabilityResidential buildings/infrastructure
5SL6502-7 — Electrical & Protection
ParameterValue
Tripping characteristic classC
Energy limitation class3
Overvoltage categoryIII
5SL6502-7 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units2
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL6502-7 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens SENTRON 5SL6502-7 is a 1P+N miniature circuit breaker rated 2 A with a C-curve trip characteristic, designed for 230 V AC single-phase circuits. Its 6 kA breaking capacity per EN 60898 (and matching 6 kA per IEC 60947-2) covers residential and light commercial distribution boards where fault levels stay under that threshold. At 2 A it's sized for low-current final subcircuits, not motor or transformer primaries.

Depth is 76 mm, installation depth 70 mm, so it sits flush with other SENTRON 5SL-series breakers in a distribution board. IP20 with conductors connected — fine inside a closed panel, not for wet locations. Sealable cover is standard — useful for utility-metering or tamper-proof installations.

The 6 kA breaking capacity per EN 60898 is the standard domestic rating in most European markets — adequate for TN and TT systems where the prospective short-circuit current at the board doesn't exceed 6 kA. The same 6 kA per IEC 60947-2 gives industrial certification for the same fault level. Power loss is 1.2 W per pole in hot operating state at rated current. In a densely populated board with multiple breakers running near rating, that heat adds up — factor it into enclosure thermal calculations.

Frequently asked questions

What is the breaking capacity of the 5SL6502-7?

6 kA per EN 60898 and 6 kA per IEC 60947-2 at 230 V AC. That's the standard domestic and light-commercial rating for this class of MCB.

Will the 5SL6502-7 drop into a panel designed for the 5SL4363-7?

Not without rewiring — the 5SL6502-7 is 1P+N (2-pole, switched neutral) while the 5SL4363-7 is a 3-pole breaker. Both share the same 76 mm depth and 90 mm height, but the 5SL6502-7 is 36 mm wide (2 MW) versus 54 mm (3 MW) for the 5SL4363-7, so the DIN-rail footprint and wiring differ.

Where can I buy the 5SL6502-7?

Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers published here.