Breaking capacity and standards
DIN-rail footprint and derating
Mounting position is any, so you can lay it horizontally or vertically inside a shallow enclosure. Rated 10 A at 30 °C ambient. At 40 °C derate to 9.3 A; at 45 °C to 9 A. If your panel runs warm — near a transformer or in a sealed enclosure — use the derated figure for the continuous load.
Construction and environmental
Halogen-free and silicon-free construction, sealable with a lead or tag, and touch-protected terminals. IP20 with connected conductors — fine inside a cabinet, not for wet locations. Mechanical life is 20 000 switching cycles typical.