B-curve and thermal derating
Rated 13 A at 30 °C ambient; derates to 12.37 A at 40 °C and 11.36 A at 55 °C, so if the panel runs warm size the load accordingly.
Two modular-width units (36 mm wide) snap onto DIN rail; mounting position any. IP20 with connected conductors — keep it inside a distribution board, not in a wet location.