Skip to main content
Siemens 5SL6532-7BB — 1-Pole MCB (DIN Rail)

5SL6532-7BB SENTRON MCB, 32 A, C-curve, 2-pole, 6 kA

MPN5SL6532-7BB

Siemens SENTRON 5SL6 series, 5SL6532-7BB miniature circuit breaker, 32 A, C-curve, 2-pole 1P+N, 6 kA breaking capacity per EN 60898, 230 V AC, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6532-7BB — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityResidential buildings/infrastructure
5SL6532-7BB — Electrical & Protection
ParameterValue
Tripping characteristic classC
Rated value (EN 60898)6 kA
Overvoltage category3
5SL6532-7BB — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SL6532-7BB — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

What this MCB does in the panel

The Siemens SENTRON 5SL6532-7BB is a 2-pole miniature circuit breaker (1P+N) rated 32 A at 230 V AC with a C tripping curve — meaning it holds through moderate inrush (motor starts, capacitor banks) and trips on sustained overloads between 5× and 10× rated current. The neutral pole switches as well, so you get full isolation on both conductors when the breaker opens.

The screw terminals accept solid or stranded copper from 0.75 mm² up to 25 mm², tightened to 2.5–3 N·m. That 25 mm² top end means you can feed a 32 A circuit with a single 6 mm² or even 10 mm² conductor without pigtailing down.

Frequently asked questions

Where can I buy 5SL6532-7BB and how do I get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote to confirm current availability and pricing.

Will 5SL6532-7BB drop into a panel specified around 5SL6563-7BB without rewiring?

Both are 2-pole 1P+N SENTRON 5SL6 breakers sharing the same DIN-rail footprint (36 mm width, 70 mm installation depth) and terminal range (0.75–25 mm² solid/stranded). The difference is the rating: 5SL6532-7BB is 32 A C-curve, while 5SL6563-7BB is 63 A C-curve. If the panel's busbar and downstream wiring are sized for 63 A, dropping in a 32 A breaker works electrically but may nuisance-trip on loads that draw above 32 A. No rewiring needed — same mechanical fit.

What is 5SL6532-7BB's listed depth (76 mm) on this component line?

The overall depth is 76 mm; the installation depth behind the DIN rail is 70 mm.

What is 5SL6532-7BB's listed solid (0.75... 25 mm²) on this component line?

The screw terminals accept solid copper conductors from 0.75 mm² up to 25 mm².

MPN
5SL6532-7BB