Siemens 5SL6550-6 — 1-Pole MCB (DIN Rail)

Siemens 5SL6550-6 SENTRON MCB, 50A 1P+N B-Curve 6kA

MPN5SL6550-6
Active

Siemens SENTRON 5SL6 series, 5SL6550-6 miniature circuit breaker, 1P+N, 50 A, B characteristic, 6 kA, 230/250 V AC.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL6550-6 — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameSENTRON
Number of poles2
Application suitabilityResidential buildings/infrastructure
5SL6550-6 — Electrical & Protection
ParameterValue
Tripping characteristic classB
Rated value (EN 60898)6 kA
Overvoltage category3
5SL6550-6 — Mounting & Connection
ParameterValue
Mounting positionany
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
SealableYes
5SL6550-6 — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens 5SL6550-6 is a 1P+N miniature circuit breaker from the SENTRON 5SL6 series, rated 50 A at 230 V AC with a B tripping characteristic. The B curve trips between 3 and 5 times rated current (150–250 A), making it the standard choice for resistive and general-purpose loads in residential and infrastructure installations — lighting circuits, socket outlets, and small distribution boards where inrush is moderate. Breaking capacity is 6 kA per both EN 60898 and IEC 60947-2, adequate for most domestic and light commercial service entrances where the prospective short-circuit current stays under that threshold.

Panel fit and wiring constraints

Two width units (36 mm) on the DIN rail, installation depth 70 mm, total depth 76 mm. Accepts solid or stranded copper from 0.75 mm² up to 25 mm².

Frequently asked questions

What conductor sizes does 5SL6550-6 accept?

Solid or stranded copper from 0.75 mm² up to 25 mm², terminated at 2.5–3 N·m.

Will 5SL6550-6 drop into a panel specified around 5SL6563-7BB without rewiring?

Both are 1P+N 5SL6-series breakers on the same 36 mm DIN-rail footprint, so the mechanical fit is identical. The difference is the rating: 5SL6550-6 is 50 A B-curve; 5SL6563-7BB is a different current/characteristic. Check your circuit's load and trip coordination before swapping.

MPN
5SL6550-6