At 30 °C ambient the breaker carries the full 16 A; at 40 °C it derates to 15.28 A, at 50 °C to 14.53 A, and at 55 °C to 14.14 A. If the panel runs warm — say a crowded enclosure near a transformer — use the 40 °C figure for the BOM line. The breaker occupies 4 modular width units (72 mm wide, 90 mm high, 76 mm deep with 70 mm installation depth) and snaps onto standard DIN rail.
Siemens 5SL6616-7CC SENTRON MCB, 3P+N, C-16A, 6kA
Siemens SENTRON miniature circuit breaker, 3P+N, C characteristic, 16 A rated at 400 V AC, 6 kA breaking capacity per EN 60898, 4 MW units, IP20.
Specifications
| Parameter | Value |
|---|---|
| Brand name | SENTRON |
| Application suitability | Residential buildings/infrastructure |
| Parameter | Value |
|---|---|
| Number of poles | 4 |
| Pole configuration | 3P+N |
| Rated current (In), AC | 16 A |
| Rated voltage, AC (multi-phase) | 440 V |
| Rated voltage, DC (max.) | 72 V |
| Parameter | Value |
|---|---|
| Tripping characteristic (trip curve) | C |
| Rated breaking capacity (Icn), per EN 60898 | 6 kA |
| Energy limitation class | 3 |
| Overvoltage category | III |
| Pollution degree | 2 |
| Degree of protection (IP) | IP20, with connected conductors |
| Touch protection | Yes |
| Parameter | Value |
|---|---|
| Width in modular units | 4 |
| Width | 72 mm |
| Height | 90 mm |
| Depth | 76 mm |
| Installation depth | 70 mm |
| Mounting position | any |
| Tightening torque, max. | 75 °C |
| Tightening torque, min. | -40 °C |
| Sealable | Yes |
| Parameter | Value |
|---|---|
| Halogen-free | Yes |
| Silicone-free | Yes |
Product details
Frequently asked questions
What is the breaking capacity of 5SL6616-7CC?
The breaking capacity is 6 kA per EN 60898 at 400 V AC. That rating is tested and certified under the standard for miniature circuit breakers in residential and infrastructure panels.
What is the difference between 5SL6616-7CC and 5SL3116-6MB?
The 5SL6616-7CC is a 3P+N (4-pole) breaker with neutral switching, while the 5SL3116-6MB is a single-pole unit. The 5SL6616-7CC will not drop into a panel wired for a single-pole breaker without rewiring the busbar and neutral connection. They share the same SENTRON family and C characteristic, but the pole count and neutral switching are different.
Where can I buy 5SL6616-7CC?
This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.