Skip to main content
Siemens 5SL6632-7CC — 4-Pole MCB (DIN Rail)

Siemens 5SL6632-7CC SENTRON MCB, 4P C-32A 6kA, 400V AC

MPN5SL6632-7CC
Active

Siemens SENTRON 5SL6CC series, 5SL6632-7CC miniature circuit breaker, 4-pole 3P+N, C-curve 32 A, 6 kA breaking capacity per EN 60898, 400 V AC.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6632-7CC — Identification
ParameterValue
Type / order code5SL6CC
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL6632-7CC — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated current (In), AC32 A
Rated voltage, AC (multi-phase)440 V
Rated voltage, DC (max.)60 V
Voltage typeAC
Rated frequency50 Hz
5SL6632-7CC — Protection
ParameterValue
Tripping characteristic (trip curve)C
Rated breaking capacity (Icn), per EN 608986 kA
Overvoltage category3
Degree of protection (IP)IP20, with connected conductors
Neutral conductor switchingYes
Touch protectionYes
5SL6632-7CC — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
SealableYes
5SL6632-7CC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
Influence of ambient temperature (derating)Periodically +55°C, max. 95% humidity

Product details

What this 4-pole MCB does on the rail

The Siemens 5SL6632-7CC is a SENTRON 5SL6CC miniature circuit breaker rated 32 A at 400 V AC, C-curve tripping characteristic, 4-pole (3P+N) with switched neutral. The 6 kA breaking capacity per EN 60898 covers most residential and light commercial distribution boards — enough for a submain feeding a mixed lighting and socket-outlet circuit where the prospective fault current stays under that threshold. C-curve means the magnetic trip operates at 5 to 10 times rated current, so it holds motor inrush from small pumps or compressors but still clears a hard short fast enough to protect the downstream cable.

Mounting and wiring fit

Snaps onto standard 35 mm DIN rail — 4 width units (72 mm wide), 90 mm tall, 76 mm deep. Installation depth is 70 mm, so it clears a standard 80 mm deep enclosure backplate. Terminals accept solid or stranded conductors from 0.75 to 25 mm²; tighten to 2.5 to 3 N·m. IP20 with connected conductors — fine inside a closed panel, not for wet locations. Mounting position any, which helps when the rail is vertical or horizontal.

Frequently asked questions

What is the breaking capacity of 5SL6632-7CC?

Rated 6 kA per EN 60898 at 400 V AC — suitable for standard residential and light commercial distribution boards.

What conductor sizes does 5SL6632-7CC accept?

Solid or stranded conductors from 0.75 to 25 mm². Tightening torque 2.5 to 3 N·m.

Where can I buy 5SL6632-7CC?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
5SL6632-7CC