Skip to main content
Siemens 5SL6632-7MB — 4-Pole MCB (DIN Rail)

Siemens 5SL6632-7MB SENTRON MCB, 400V 6kA, C-Curve, 32A, 4-P

MPN5SL6632-7MB
Active

Siemens SENTRON 5SL6632-7MB miniature circuit breaker, 400 V AC, 6 kA, C-curve, 32 A, 3P+N, 4-module width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL6632-7MB — Identification
ParameterValue
Brand nameSENTRON
Application suitabilityResidential buildings/infrastructure
5SL6632-7MB — Ratings
ParameterValue
Number of poles4
Pole configuration3P+N
Rated voltage, AC (multi-phase)440 V
5SL6632-7MB — Protection
ParameterValue
Tripping characteristic (trip curve)C
Energy limitation class3
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL6632-7MB — Mechanical
ParameterValue
Width in modular units4
Width72 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL6632-7MB — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL6632-7MB — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)3.1 W

Product details

The Siemens SENTRON 5SL6632-7MB is a 4-pole (3P+N) miniature circuit breaker rated 400 V AC, 32 A, with a C tripping characteristic and 6 kA breaking capacity per EN 60898 and IEC 60947-2.

Snaps onto standard DIN rail — any mounting position works, which helps when you're retrofitting into a crowded panel.

Key ratings in plain terms

The 32 A rating handles a 7.5 kW three-phase motor at 400 V (roughly) or a cluster of resistive loads up to that line current. Mechanical life is 20,000 cycles typical — that's plenty for a distribution breaker that cycles rarely.

Material and environmental specs

Frequently asked questions

Where can I buy 5SL6632-7MB and how do I get a price?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is 5SL6632-7MB's listed depth (76 mm) on this component line?

The depth is exactly 76 mm, with an installation depth of 70 mm (the additional 6 mm accounts for the front handle projection). Width is 72 mm (4 modular units), height is 90 mm.

Will 5SL6632-7MB drop into a panel that was specified around 5SL4363-7 without rewiring?

Not without changes. The 5SL4363-7 is a 3-pole breaker (3P) with 10 kA breaking capacity, while the 5SL6632-7MB is 4-pole (3P+N) with 6 kA. The 5SL4363-7 is 3 modular units wide (54 mm), the 5SL6632-7MB is 4 units wide (72 mm), so it won't fit the same DIN-rail footprint without a wider panel or a filler. The neutral pole also means you need a neutral conductor run to the breaker, which the 3-pole version didn't require.

MPN
5SL6632-7MB