The part carries a typical mechanical service life of 20,000 operating cycles, which is double the 10,000 cycles specified on the 3-pole 5SL4363-7 sibling. This reflects the additional wear margin on the switched neutral pole in the 3P+N design.
Halogen-free and silicon-free construction per the spec, which matters for panels in clean-room or high-reliability environments where outgassing can contaminate contacts or optics.
Electrical ratings
Power loss per pole is 3.3 W at rated current in hot operating state, giving a total of 13.2 W for the 4-pole assembly. This should be factored into the enclosure thermal budget, especially when breakers are ganged in a multi-way board.