Skip to main content
Siemens 5SL7116-7RC — 1-Pole MCB (DIN Rail)

Siemens Betagard 5SL7116-7RC MCB, 1P C16, 15/20 kA

MPN5SL7116-7RC

Siemens Betagard 5SL7116-7RC miniature circuit breaker, 1-pole, C-curve, 16 A, 15 kA per EN 60898, 20 kA per IEC 60947-2, 240/440 V AC, 1 MW width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL7116-7RC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameBetagard
Number of poles1
Pole design1P
Application suitabilityIndustry
5SL7116-7RC — Electrical & Protection
ParameterValue
Tripping characteristic classC
Overvoltage categoryIII
5SL7116-7RC — Mounting & Connection
ParameterValue
Mounting positionany
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Modular width units1
Torque, min.-40 °C
Torque, max.75 °C
SealableYes
5SL7116-7RC — Environmental
ParameterValue
IP protection classIP20, with connected conductors
Pollution degree2
Halogen-freeYes
Silicone-freeYes

Product details

The Siemens Betagard 5SL7116-7RC is a 1-pole miniature circuit breaker with a C-curve trip characteristic, rated 16 A. It carries a 15 kA breaking capacity per EN 60898 and 20 kA per IEC 60947-2, making it suitable for industrial branch-circuit protection where higher fault currents are expected than residential-grade MCBs handle. Rated for single-phase operation at 240 V AC and multi-phase at 440 V AC, 50/60 Hz.

Breaking capacity and trip curve

The 15 kA rating under EN 60898 is the standard for final circuits in buildings; the 20 kA under IEC 60947-2 covers industrial panel applications where the prospective short-circuit current is higher. The C-curve (5–10× In) is the default for general-purpose loads — lighting, small motor circuits, control transformers — where inrush is moderate. That figure matters for thermal coordination inside a crowded enclosure — 1.7 W per pole is low enough that derating is minimal in a standard 20 °C ambient.

Dimensions: 90 mm high, 76 mm deep, 18 mm wide — fits a standard 1 MW DIN-rail slot. Installation depth is 70 mm, leaving 6 mm behind the rail for wiring clearance. Sealable with a lead seal or adhesive label to prevent tamper — common for utility-metering or tenant-submetering applications. Vibration-resistant per IEC 60068-2-6; mechanical life is 10 000 operating cycles typical.

Frequently asked questions

Where can I buy 5SL7116-7RC and get a price?

The 5SL7116-7RC is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm quote.

What is the breaking capacity of 5SL7116-7RC?

15 kA per EN 60898 and 20 kA per IEC 60947-2. The higher IEC figure applies when the MCB is used in an industrial panel with a higher prospective short-circuit current.

Will 5SL7116-7RC drop into a panel specified for 5SL6006-7?

Both are 1 MW wide, same 18 mm footprint and 76 mm depth. The 5SL7116-7RC has a higher breaking capacity (15/20 kA vs 6 kA) and is rated for 240/440 V AC vs 230 V AC. It fits the same DIN-rail slot but check the upstream fault level — the Betagard is a different brand line (Betagard vs SENTRON) so panel documentation may need updating.