The 5SL7206-8RC: At 30 °C ambient, it carries the full 6 A; at 40 °C it derates to 5.64 A, and at 60 °C to 4.86 A — so if your enclosure runs warm, size your load against the derated figure, not the label.
Snap-on DIN rail mount, 2 modular width units (18 mm per unit). Mounting position any, so you can lay it sideways in a tight gland plate if needed.
Current-production part. The Betagard line is halogen-free and silicon-free, sealable for lockout/tagout.