Siemens 5SL7210-3RC Betagard MCB, 2P K-Char 10A 15kA

MPN5SL7210-3RC

Siemens Betagard 5SL7210-3RC miniature circuit breaker, 2-pole, K characteristic, 10 A rated, 15 kA breaking capacity per IEC 60898 and IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL7210-3RC — Identification
ParameterValue
Product designationMiniature circuit breaker
Brand nameBetagard
5SL7210-3RC — Electrical
ParameterValue
Number of poles2
5SL7210-3RC — Protection
ParameterValue
Tripping characteristic classK
Overvoltage categoryIII
5SL7210-3RC — Mechanical
ParameterValue
Modular width units2
Width36 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Min.-40 °C
Max.75 °C
Protection degree (IP)IP20, with connected conductors
5SL7210-3RC — Environmental
ParameterValue
Pollution degree3

Product details

K-characteristic 2-pole MCB for motor and inductive loads

The Siemens 5SL7210-3RC is a Betagard miniature circuit breaker with a K tripping characteristic, designed for 2-pole protection at 10 A rated current. The K curve provides a magnetic trip threshold of 8 to 12 times In, making it suited for motor circuits and transformer-fed loads where inrush currents exceed those of resistive circuits.

Temperature derating and voltage ratings

Rated current is 10 A at 50 °C ambient, with a published derating table: 10.9 A at 30 °C, 10.5 A at 40 °C, 10.2 A at 45 °C, 9.8 A at 55 °C, and 9.5 A at 60 °C. Operating voltage is 415 V AC single-phase or 440 V AC multi-phase; DC rating is 72 V maximum.

Panel integration and environmental limits

Mounting position is any orientation. IP20 protection with connected conductors, so it belongs inside a sealed enclosure in washdown or outdoor locations. Sealable design allows lockout-tagout compliance. Halogen-free and silicon-free construction.

Frequently asked questions

What is the K characteristic used for on this MCB?

The K characteristic trips magnetically at 8 to 12 times rated current, which is designed for motor and inductive loads that draw high inrush on startup. It avoids nuisance tripping that a B or C curve would cause on those loads.

What are the key ratings of the 5SL7210-3RC?

2-pole, 10 A rated, 15 kA breaking capacity per EN 60898 and IEC 60947-2, 415 V AC single-phase / 440 V AC multi-phase, 72 V DC max. Temperature derating applies above 50 °C.