It breaks fault currents up to 15 kA per EN 60898 and 20 kA per IEC 60947-2 at 415 V AC.
Rated 20 A at 30 °C ambient, but derate to 18.8 A at 40 °C and down to 16.2 A at 60 °C. The 2-pole configuration (2P design) switches both phase and neutral, or two phases in a split-phase system.
Snaps onto standard DIN rail, 2 modular width units (18 mm per unit, 36 mm total). Installation depth is 70 mm from the rail face; overall depth 76 mm. Mounting position is unrestricted — horizontal, vertical, or upside-down. IP20 with connected conductors, so it belongs inside an enclosed panel, not exposed to washdown or dust.