Mount in any position. Temperature derating is published: 63 A at 30 °C, 59.85 A at 40 °C, 56.7 A at 50 °C, 54.18 A at 60 °C. If your panel ambient runs 50 °C, you're looking at 56.7 A continuous — plan your load accordingly. Three poles = 16.5 W total heat to shed inside the enclosure.
Halogen-free and silicon-free construction. Sealable — useful if your site requires lockout-tagout on the breaker handle.