Skip to main content
Siemens 5SL7363-8RC — Miniature Circuit Breakers (MCB)

Siemens Betagard 5SL7363-8RC MCB, 3P D 63 A, 10 kA, 415 V AC

MPN5SL7363-8RC

Siemens Betagard 5SL7363-8RC, miniature circuit breaker, 3-pole, D tripping characteristic, 63 A, 10 kA breaking capacity, 415 V AC, 3 modular width units.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SL7363-8RC — Ratings
ParameterValue
Overvoltage categoryIII
5SL7363-8RC — Mechanical
ParameterValue
Width18 mm
Height90 mm
Depth76 mm

Product details

The Siemens Betagard 5SL7363-8RC is a 3-pole miniature circuit breaker with a D tripping characteristic, rated 63 A at 415 V AC. The 10 kA breaking capacity is certified per both EN 60898 (household / commercial standard) and IEC 60947-2 (industrial standard), so it can safely interrupt a fault current up to 10,000 A without welding its contacts or cascading damage upstream. At 63 A and 415 V, this is a main or heavy-feeder breaker in a 3-phase panel, not a branch-circuit device for lighting or general-purpose receptacles.

The 5SL7363-8RC occupies 3 modular width units (18 mm per unit, 54 mm total) and installs on a standard DIN rail. Mounting position is unrestricted — vertical, horizontal, or inverted — which simplifies layout in a crowded enclosure. The IP20 rating (with connected conductors) means it is protected against solid objects larger than 12.5 mm but not against moisture; it belongs inside a panel with a sealed door, not in a washdown zone.

The breaker is sealable, meaning the toggle can be locked in the off position with a padlock for lockout/tagout. Mechanical service life is 10,000 operating cycles typical; power loss per pole at rated current in hot state is 5.1 W — factor that into thermal calculations for a multi-breaker enclosure.

Frequently asked questions

What is the breaking capacity of the 5SL7363-8RC?

10 kA per both EN 60898 and IEC 60947-2 at 415 V AC. That rating holds for the 3-pole configuration.

What is the tripping curve and what loads is it suited for?

D-curve, meaning magnetic trip between 10 and 20 times the rated current (630–1260 A for this 63 A unit). It is designed for loads with high inrush — motors, transformers, welding machines — where a C-curve would nuisance-trip on startup.

Where can I buy the 5SL7363-8RC?

We source this part to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Will the 5SL7363-8RC fit in a panel designed for the 5SL4363-7?

The 5SL7363-8RC is 3 modular width units (54 mm) wide, same as the 5SL4363-7. Depth (76 mm) and installation depth (70 mm) are also identical. The DIN-rail clip and terminal layout are the same Betagard/SENTRON family. It will drop in without rewiring or panel modification, provided the D-curve and 63 A rating match the circuit requirements.

MPN