Skip to main content
Siemens 5SL7410-7RC — 4-Pole MCB (DIN Rail)

Siemens Betagard 5SL7410-7RC MCB, 4P C 10 A 15 kA EN 60898

MPN5SL7410-7RC

Siemens Betagard miniature circuit breaker, 5SL7410-7RC, 4-pole, C-curve, 10 A, 415 V AC, 15 kA (EN 60898) / 20 kA (IEC 60947-2), 4 modular width units.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SL7410-7RC — Identification
ParameterValue
Brand nameBetagard
Application suitabilityIndustry
5SL7410-7RC — Ratings
ParameterValue
Number of poles4
Pole configuration4P
Rated voltage, AC (multi-phase)440 V
5SL7410-7RC — Protection
ParameterValue
Tripping characteristic (trip curve)C
Overvoltage categoryIII
Pollution degree2
Degree of protection (IP)IP20, with connected conductors
5SL7410-7RC — Mechanical
ParameterValue
Width in modular units4
Width18 mm
Height90 mm
Depth76 mm
Installation depth70 mm
Mounting positionany
Tightening torque, max.75 °C
Tightening torque, min.-40 °C
SealableYes
5SL7410-7RC — Environmental
ParameterValue
Halogen-freeYes
Silicone-freeYes
5SL7410-7RC — Performance
ParameterValue
Power loss per pole, AC (hot state, at In)1.1 W

Product details

What this 4-pole C-curve MCB is for

Four modular width units (18 mm each) mean it occupies 72 mm of rail — standard for a 4-pole MCB in this class. The IP20 enclosure with connected conductors is typical for enclosed panel mounting; not for wet or outdoor locations without a secondary enclosure.

Two breaking-capacity ratings let you match the standard that governs your panel design. Under EN 60898 (household / similar installations) it is rated 15 kA; under IEC 60947-2 (industrial switchgear) it is rated 20 kA. At 20 kA it clears faults without cascading to upstream devices, preserving selectivity in a multi-level distribution scheme. Power loss is 1.1 W per pole in hot operating state — low enough that thermal buildup in a densely populated enclosure is manageable.

Snap-on DIN rail mounting, any position.

Frequently asked questions

What are the key ratings of the 5SL7410-7RC?

4-pole C-curve MCB rated 10 A at 415 V AC, with breaking capacity 15 kA per EN 60898 and 20 kA per IEC 60947-2. It occupies 4 modular width units (72 mm) on a DIN rail.

Where can I buy the 5SL7410-7RC?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the difference between the 5SL7410-7RC and the 5SL4363-7?

The 5SL4363-7 is a 3-pole SENTRON MCB rated 10 kA (both EN 60898 and IEC 60947-2) at 400 V AC, versus the Betagard 5SL7410-7RC which is 4-pole with higher breaking capacity (15/20 kA) at 415 V. The 5SL4363-7 is also labeled for residential/infrastructure use, while the 5SL7410-7RC is rated for industry. They are not direct drop-in replacements due to pole count and footprint differences.

MPN
5SL7410-7RC