Skip to main content
Siemens 5SM1344-6KK01 — Residual Current Breakers (RCCB/RCBO)

SENTRON 5SM1344-6KK01 RCCB, 4-pole 40 A Type A 30 mA

MPN5SM1344-6KK01

Siemens SENTRON 5SM1 series, RCCB (residual current circuit breaker), 4-pole, 40 A rated at 400 V AC, Type A, 30 mA trip, short-time delayed, DIN rail mount.

$992.53Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM1344-6KK01 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM1344-6KK01 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SM1344-6KK01 — Mechanical
ParameterValue
Mounting positionany
Installation depth55 mm
5SM1344-6KK01 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SM1344-6KK01 is a 4-pole RCCB rated 40 A at 400 V AC, 50 Hz, with a 30 mA trip threshold and Type A fault current sensitivity. It mounts on DIN rail and occupies 4 width units.

The 40 A current rating holds at ambient temperatures up to 45 °C without derating; above that, the allowable current drops in steps — 38.4 A at 50 °C, 36.8 A at 55 °C, 35.2 A at 60 °C, 33.6 A at 65 °C, and 32 A at 70 °C. Type A detects both sinusoidal AC residual currents and pulsating DC residual currents, covering most modern electronics and single-phase rectifier loads. Conductor termination accepts solid or stranded wire from 1.5 mm² to 25 mm², with a screw-terminal torque range of 2.5 to 3 N·m.

Mounting and integration notes

Mounts on DIN rail (REG) in any position — no orientation restrictions. Installation depth is 55 mm, fitting standard 60 mm deep enclosures. Supply can enter from top or bottom. Finger and back-of-hand safe construction meets the touch-protection requirements for panel builders working live.

Frequently asked questions

What conductor sizes does 5SM1344-6KK01 accept?

Solid and stranded conductors from 1.5 mm² up to 25 mm², terminated with screw-type terminals torqued to 2.5–3 N·m.

Will 5SM1344-6KK01 drop into a panel specified around 5SY4304-7CV without rewiring?

Both are 4-pole RCCBs on DIN rail with 4 width units, so the physical footprint is the same — no panel modification needed for the mounting. But the 5SM1344-6KK01 is short-time delayed and Type A; if the original 5SY4304-7CV was a different type (e.g., Type AC or instant trip), the protection characteristics differ. Compare the nameplate trip rating, delay behavior, and fault current type before swapping.

MPN