Skip to main content
Siemens 5SM1614-0 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SM1614-0 RCCB, 2-pole 40A 300mA AC, 230V

MPN5SM1614-0

Siemens SENTRON 5SM1 series RCCB, 2-pole, type AC, 40 A rated, 300 mA trip, 230 V AC, instantaneous, DIN rail mount.

$32.02Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SM1614-0 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM1614-0 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM1614-0 — Mechanical
ParameterValue
Mounting positionany
Installation depth55 mm
5SM1614-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SM1614-0 is a 2-pole residual current circuit breaker (RCCB) from the 5SM1 series, type AC, rated for 40 A at 230 V AC with a 300 mA residual trip threshold.

Thermal derating and conductor range

The 40 A rating holds at 45 °C ambient; above that, current must be derated stepwise — 38.4 A at 50 °C, 36.8 A at 55 °C, down to 32 A at 70 °C. Terminal capacity accepts solid or stranded conductors from 1 to 16 mm², with a tightening torque of 2.5 to 3 N·m on the screw terminals. The IP20 rating applies once installed in a distribution board with conductors connected — not a standalone outdoor device.

DIN-rail integration and mounting

Installation depth is 55 mm, fitting most 80 mm deep enclosures. The device is finger and back-of-hand safe per protection class. Overvoltage category III suits it for fixed installation downstream of the utility meter.

Frequently asked questions

What are the key ratings of the 5SM1614-0?

It is a 2-pole, type AC RCCB rated 40 A at 230 V AC with a 300 mA residual trip current, instantaneous trip characteristic, and a 10 kA SCCR.

Where can I buy the 5SM1614-0?

This part can be sourced to order against an RFQ through independent distribution channels; availability and current pricing are confirmed at quote time.

What conductor sizes does the 5SM1614-0 accept?

The screw terminals accept solid or stranded conductors from 1 to 16 mm², with a tightening torque of 2.5 to 3 N·m.

Does the 5SM1614-0 drop into a panel designed for the 5SL6550-7BB?

Both are 2-pole DIN-rail RCCBs with similar form factor, but the 5SL6550-7BB is a 50 A, 300 mA type AC unit while the 5SM1614-0 is 40 A. They share the same mounting footprint, so physical fit is the same; the current rating difference may affect selectivity in the panel design.

MPN
5SM1614-0