Skip to main content
Siemens 5SM1656-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM1656-6 SENTRON RCCB, 4P, 63A, 300mA, Type A, 10kA

MPN5SM1656-6

Siemens SENTRON 5SM1 series RCCB, 4-pole, 63 A rated at 40 °C, 300 mA Type A residual current, 10 kA short-circuit current rating, DIN rail mount, instantaneous.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SM1656-6 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM1656-6 — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM1656-6 — Mechanical
ParameterValue
Mounting positionany
Installation depth55 mm
5SM1656-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM1656-6 is a SENTRON 5SM1-series residual current circuit breaker (RCCB), 4-pole, rated 63 A at 40 °C and 45 °C, with a 300 mA Type A tripping characteristic and a 10 kA short-circuit current rating. It mounts on DIN rail (REG), occupies 4 width units (about 72 mm), and installs 55 mm deep — a standard panel footprint for a 4P RCCB. Instantaneous design (no short-time delay) means it trips within 40 ms at rated residual; use it where selectivity against upstream delayed RCCBs is not required. Rated supply voltage is 500 V AC, overvoltage category III, so it handles the utility-side transient environment typical of main distribution boards and sub-distribution panels. Finger and back-of-hand safe per the protection-against-electrical-shock listing — the terminals are shrouded enough for live-panel work with the deadfront on.

Full 63 A holds up to 45 °C ambient. Above that, derate: 60.48 A at 50 °C, 57.96 A at 55 °C, 55.44 A at 60 °C, 52.92 A at 65 °C, 50.4 A at 70 °C. If the panel internal temperature exceeds 45 °C — common in a crowded enclosure with upstream breakers — the 50 °C derating line is the one to design against. Terminal torque spec is 2.5 to 3 N·m, accepting solid or stranded conductors from 1.5 mm² up to 25 mm² — covers the full range for a 63 A circuit on standard PVC copper.

The closest functional peer from the same brand is the 5SQ2670-2YA63 — same poles, same current, same Type A residual — but the 5SQ series carries a different internal construction (short-time delayed vs instantaneous). Verify the selectivity requirement before swapping; the 5SM1656-6 is instantaneous, so it will trip ahead of a delayed upstream device.

Approvals and compliance paperwork

The 5SM1656-6 is silicon-free, which matters for potting or conformal-coating processes in high-vibration or corrosive environments. Mechanical endurance is rated at 10 000 switching cycles typical; the I²t let-through is 70 000 A²·s, and surge current withstand is 1 kA.

Frequently asked questions

What conductor sizes does 5SM1656-6 accept?

Solid and stranded conductors from 1.5 mm² up to 25 mm². Terminal torque spec is 2.5 to 3 N·m.

MPN
5SM1656-6