Siemens 5SM2333-0 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SM2333-0 RCD Unit, 40 A, 30 mA, 3-Pole

MPN5SM2333-0
Active

Siemens SENTRON RCD unit, instantaneous, AC type, 3-pole, 40 A rated current, 30 mA fault current, 50 Hz, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SM2333-0 — Electrical Ratings
ParameterValue
Number of poles3
Overvoltage categoryIII
5SM2333-0 — Identification
ParameterValue
Product designationRCD-unit
Product design / constructioninstantaneous
5SM2333-0 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width105 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SM2333-0 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

It's an instantaneous type (no time delay), designed for AC residual currents only, and built to snap onto a DIN rail in a standard distribution board — 3 modular width units wide, 70 mm deep.

The 40 A rating at AC is the continuous current it can carry in a 50 Hz circuit — sized for a sub-feed or a group of downstream breakers. The 30 mA trip threshold covers personnel protection (shock hazard) per IEC 60364. Because it's instantaneous, it trips within milliseconds on a fault, but that also means it's not suitable where you need a short time delay to ride through inrush or to coordinate with downstream RCDs. The insulation voltage is 460 V, and it withstands a 4 kV surge — overvoltage category III, so it's at home in the main distribution panel, not just sub-boards.

Temperature derating — the real-world current

Above that, it derates: 37.2 A at 45 °C, 36 A at 50 °C, 34.8 A at 55 °C, 34 A at 60 °C, 33.2 A at 65 °C, and 32 A at 70 °C. If your panel runs warm — say, a packed enclosure near a drive cabinet — the 32 A floor at 70 °C is the number to use for your load calculation.