Skip to main content
Siemens 5SM2336-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM2336-6 SENTRON RC Unit, 63A 30mA Type A, 3-Pole

MPN5SM2336-6
Active

Siemens SENTRON 5SM2336-6 RC unit, 3-pole, Type A, 63 A rated current, 30 mA trip sensitivity, for 5SL4 miniature circuit breaker, DIN-rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SM2336-6 — Electrical Ratings
ParameterValue
Number of poles3
Overvoltage categoryIII
5SM2336-6 — Identification
ParameterValue
Product designationRC unit
Product design / constructionInstantaneous
5SM2336-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum45 °C
Minimum-25 °C
Width105 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SM2336-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM2336-6 is a residual current unit (RC unit) from the SENTRON family, designed to pair with a 5SL4 miniature circuit breaker to form an RCBO. It's a 3-pole, Type A device rated at 63 A with a 30 mA trip threshold — the standard sensitivity for personnel protection against direct contact. Type A detection means it catches sinusoidal AC faults plus pulsating DC residual currents, which covers most modern electronic loads like switched-mode power supplies and variable-speed drives.

Fit and mounting — panel integration

Snaps onto DIN rail (REG profile per), occupying 3 modular width units. The 70 mm depth matches the standard 5SL4 MCB it clips to, so the combined RCBO assembly sits flush in a distribution board. IP20 rating applies once installed with conductors connected — expected for enclosed panel gear. Silicon-free construction matters for applications like automotive paint shops or electronics assembly where silicone outgassing can cause adhesion or contact failures.

Thermal performance — the derating curve matters

Above that, the device derates linearly: 58.6 A at 40 °C, 58.59 A at 45 °C, 56.7 A at 50 °C, 54.81 A at 55 °C, 53.55 A at 60 °C, 52.29 A at 65 °C, and 50.4 A at 70 °C.

Key electrical specs at a glance

Surge current resistance is rated at 1 kA, meaning it can withstand a single lightning-induced surge of that magnitude without failing. Operating frequency is 50 Hz only; this is not a 50/60 Hz universal device. The RC unit is instantaneous (no short-time delay), so it trips immediately on a fault. That's appropriate for personnel protection, but if you need selectivity with downstream RCDs, you'd want a delayed (S-type) unit instead.

Compliance documentation

As a SENTRON device, the 5SM2336-6 is designed and tested to IEC/EN 61008 and related standards for residual current devices. The manufacturer provides the standard declaration of conformity, CE marking, and — upon request — the detailed test certificate. RoHS and REACH compliance documentation is available through the standard documentation package.

Frequently asked questions

Where can I buy the 5SM2336-6 and how is it quoted?

The 5SM2336-6 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What are the key ratings of the 5SM2336-6?

63 A rated current, 30 mA trip sensitivity, Type A residual current detection, 3-pole, 460 V insulation voltage, 50 Hz only, instantaneous trip characteristic.

What is the 5SM2336-6's depth?

The depth is 70 mm, which matches the 5SL4 MCB it pairs with for a flush RCBO assembly.

What compliance documentation does Siemens provide for this part?

Standard documentation includes CE declaration of conformity, RoHS and REACH compliance statements, and the IEC/EN 61008 test certificate — all available through the standard documentation request process.

MPN
5SM2336-6