Skip to main content
Siemens 5SM2642-6 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM2642-6 SENTRON RCD, 4-Pole 40 A 300 mA Type A

MPN5SM2642-6
Active

Siemens SENTRON, RCD-unit, 4 poles, 40 A rated at AC, 300 mA Type A, instantaneous, 50 Hz, IP20.

$26.85Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SM2642-6 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM2642-6 — Identification
ParameterValue
Product designationRCD-unit
Product design / constructioninstantaneous
5SM2642-6 — Mechanical
ParameterValue
Mounting positionany
Width in modular units3
Maximum75 °C
Minimum-40 °C
Width124 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SM2642-6 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

Instantaneous design — no adjustable delay — so it clears ground faults as fast as the fault current drives it, which matters for personnel protection in circuits where selectivity isn't the primary concern. Type A detection covers sinusoidal AC and pulsating DC residual currents, the standard for most mixed-load panels with electronics, drives, or rectifiers.

Rated 40 A at AC, but the thermal derating curve is worth noting for a warm panel: at 40 °C it's 37.2 A, at 50 °C it's 36 A, and at 70 °C it drops to 32 A.

Occupies 3 modular width units on DIN rail (124 mm wide, 90 mm tall, 77 mm deep, 70 mm installation depth). Mounts in any position; supply can land top or bottom. Not sealable, so no padlock hasp for lockout/tagout on the device itself.

Designed for 50 Hz systems. Rated fault current is fixed at 300 mA — not adjustable. Surge current resistance 1 kA, surge voltage resistance 4 000 V. False tripping protection function is present. The product variation is listed as for 5SY, meaning it pairs mechanically and electrically with Siemens 5SY MCBs for a combined RCBO assembly in the same footprint.

Frequently asked questions

What is the 5SM2642-6 rated current and trip threshold?

Rated 40 A at AC with a 300 mA Type A residual current trip. Type A covers AC and pulsating DC fault currents.

Where can I buy 5SM2642-6 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

Does 5SM2642-6 pair with a Siemens MCB?

Yes, the product variation is listed as for 5SY, meaning it mechanically and electrically couples with Siemens 5SY series miniature circuit breakers for a combined RCBO assembly.

MPN
5SM2642-6