Skip to main content
Siemens 5SM3311-0KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3311-0KL SENTRON RCCB, 2-pole, 16 A, 30 mA, 230 V

MPN5SM3311-0KL

Siemens SENTRON 5SM3 series, RCCB, 2-pole, type AC, In: 16 A, 30 mA, Un AC: 230 V, N left, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3311-0KL — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM3311-0KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM3311-0KL — Mechanical
ParameterValue
Mounting positionany
Installation depth70 mm
5SM3311-0KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The 5SM3311-0KL: This is an instantaneous RCCB — no intentional time delay — so it trips within the standard cycle on a residual fault. The 30 mA rating covers personnel protection in residential and commercial final circuits where the earth leakage path is resistive.

The 16 A rated current and 30 mA sensitivity tell you this RCCB is sized for a lighting or general-purpose socket circuit, not a high-load branch. That's fine for circuits with resistive or conventional loads, but if the downstream equipment includes VFDs, switched-mode supplies, or LED drivers that generate pulsed DC fault currents, you'd need a type A or F RCCB instead. The 5SM3311-0KL won't trip on those waveforms.

Panel integration

Mounts on DIN rail (REG) in any position. Terminals accept 1 to 16 mm² solid or stranded copper. Tightening torque is 2.5 to 3 N·m — a standard screwdriver setting, no special tool needed. The neutral connection is on the left (N left variant). IP20 with the distribution board installed and conductors connected — that's typical for panel-mount devices; the enclosure provides the environmental seal.

Frequently asked questions

What is the difference between 5SM3311-0KL and the 5SU9304-1KK32?

The 5SU9304-1KK32 is an RCBO (combined RCD and MCB) with a 32 A rating and type C trip curve, while the 5SM3311-0KL is a plain RCCB at 16 A. The RCBO is 1 module wide (18 mm) versus 2 modules for the RCCB. They are not drop-in substitutes — the RCBO adds overcurrent protection the RCCB lacks.

Where can I buy the 5SM3311-0KL?

This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time.

What wire sizes does the 5SM3311-0KL accept?

The screw terminals accept 1 to 16 mm² solid or stranded copper conductors. Tightening torque is 2.5 to 3 N·m.

MPN