Siemens 5SM3314-6LA — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3314-6LA SENTRON RCCB, 40 A, 30 mA, Type A, 2-pol

MPN5SM3314-6LA

Siemens SENTRON 5SM3 series RCCB, 2-pole Type A, 40 A rated current, 30 mA trip sensitivity, 230 V AC, with integrated thermal overload protection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3314-6LA — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM3314-6LA — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM3314-6LA — Mechanical
ParameterValue
Mounting positionany
Installation depth70 mm
5SM3314-6LA — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

It combines residual current protection with integrated thermal overload protection in a single 2-module-width package. Rated at 40 A and 30 mA trip sensitivity on a 230 V AC supply, this is a Type A device — it detects sinusoidal AC fault currents plus pulsating DC fault currents, which covers most modern electronic loads like variable-speed drives, LED drivers, and switching power supplies. The instantaneous design (no short-time delay) means it trips within milliseconds of a fault, giving fast disconnection for personnel protection. Finger and back-of-hand safe construction meets the shock-protection requirements for panel builders.

Installation and environmental fit

The screw terminals call for 2.5 to 3 N·m tightening torque. Installation depth is 70 mm. Overvoltage category III suits fixed-installation distribution boards downstream of the utility meter.

Frequently asked questions

What is the wire range for 5SM3314-6LA?

The terminals accept solid or stranded conductors from 1 to 16 mm².

Will 5SM3314-6LA drop into a panel specified around 5SY4304-7CV without rewiring?

No — the 5SY4304-7CV is a 3-pole MCB (miniature circuit breaker) with a different function (overcurrent and short-circuit protection only), while the 5SM3314-6LA is a 2-pole RCCB for earth leakage protection with integrated thermal overload. They serve different protection roles and are not drop-in interchangeable.

MPN