Siemens 5SM3318-6KK — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3318-6KK SENTRON RCCB, 2-pole, 100 A, 30 mA, Type

MPN5SM3318-6KK
Active

Siemens SENTRON 5SM3318-6KK, RCCB, 2-pole, Type A, rated current 100 A, rated residual current 30 mA, Un AC 230 V, 50 Hz, 10 kA SCCR, DIN rail mount, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

5SM3318-6KK — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM3318-6KK — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM3318-6KK — Mechanical
ParameterValue
Mounting positionany
Width in modular units2
Maximum45 °C
Minimum-25 °C
Width36 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SM3318-6KK — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SM3318-6KK is a 2-pole residual current operated circuit breaker (RCCB), Type A, rated for 100 A continuous load and 30 mA residual current sensitivity on a 230 V AC, 50 Hz supply. The 100 A rating sizes it for a main incoming supply or a high-load submain, not a branch circuit. The conditional breaking capacity per EN 60898 is listed at 1 kA when backed by an overcurrent protective device, which is the coordination value for standard domestic back-up fuses or MCBs. The 2-pole design switches both line and neutral. Mounting is on DIN rail (REG), width 2 modular units (36 mm). Depth is 70 mm, height 90 mm. The enclosure rating is IP20 only when installed in a distribution board with all conductors connected — the terminals are not touch-safe exposed. Silicon-free construction is a bonus for applications where silicone outgassing can contaminate contacts or optical surfaces, such as paint shops or clean-room adjacent panels.

The 70 mm installation depth matches the standard SENTRON distribution board depth — no need for a deeper enclosure. The instantaneous design trips on the first half-cycle of a residual fault.

Frequently asked questions

What is the closest functional second-source to 5SM3318-6KK?

The 5SL6550-7BB is a SENTRON miniature circuit breaker with the same 2-pole, 2-MW DIN rail footprint and 70 mm installation depth, but it is an MCB (50 A, C-curve) with a 6 kA breaking capacity, not an RCCB. It does not provide residual current protection. For a direct RCCB replacement, the 5SM3 series is the correct family; no second-source with identical ratings is listed in this evidence.

Will 5SM3318-6KK drop into a panel specified for 5SL6550-7BB without rewiring?

The 5SM3318-6KK shares the same 36 mm width, 90 mm height, and 70 mm installation depth as the 5SL6550-7BB, so it fits the same DIN rail slot and enclosure depth. However, the 5SL6550-7BB is a 50 A MCB, while the 5SM3318-6KK is a 100 A RCCB — the circuit must be rated for 100 A and include a neutral conductor for the RCCB to function. Rewiring is required if the existing circuit is only 50 A or lacks a switched neutral.

MPN
5SM3318-6KK