Siemens 5SM3321-4 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3321-4 SENTRON RCCB, 2-pole Type B, 16 A, 30 mA,

MPN5SM3321-4

Siemens SENTRON 5SM3321-4, 2-pole RCCB, type B, short-time delayed, 16 A rated current, 30 mA rated residual current, 230 V AC, 50/60 Hz.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

5SM3321-4 — Electrical Ratings
ParameterValue
Number of poles2
Overvoltage categoryIII
5SM3321-4 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SM3321-4 — Mechanical
ParameterValue
Mounting positionany
Width in modular units4
Maximum45 °C
Minimum-25 °C
Width72 mm
Height90 mm
Depth70 mm
Installation depth70 mm
5SM3321-4 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM3321-4 is a 2-pole residual current circuit breaker (RCCB) from the SENTRON series, designed for 230 V AC supply at 50/60 Hz. It is rated at 16 A with a 30 mA residual current sensitivity and is type B, meaning it detects AC, pulsating DC, and smooth DC fault currents — required where variable-speed drives, UPS systems, or photovoltaic inverters are on the circuit. The short-time delayed design (selective type) provides discrimination: in a fault event, the downstream RCCB trips first, leaving this unit and upstream devices undisturbed. This suits sub-distribution boards feeding multiple socket-outlet circuits or mixed loads.

Snaps onto DIN rail (REG) per EN 60715. Depth is 70 mm — verify cabinet door clearance; some shallow enclosures need the 70 mm plus wiring space. Mounting position is unrestricted, but the IP20 rating is conditional on the distribution board being installed and conductors connected.

Frequently asked questions

What is the 5SM3321-4 used for?

It is a 2-pole type B RCCB used for residual current protection in 230 V AC circuits where smooth DC fault currents may be present — such as circuits with VFDs, UPS systems, or PV inverters. The short-time delayed design provides selectivity in sub-distribution boards.

Where can I buy the 5SM3321-4?

This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of the 5SM3321-4?

The rated breaking capacity is 0.8 kA according to both EN 60898 and IEC 61008-1.