Skip to main content
Siemens 5SM3342-6KL — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3342-6KL SENTRON RCCB, 4P Type A, 25A, 30mA, 400V

MPN5SM3342-6KL

Siemens SENTRON 5SM3 series RCCB, 4-pole Type A, 25 A rated current, 30 mA trip sensitivity, 400 V AC, DIN rail mount, N-left design.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3342-6KL — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM3342-6KL — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM3342-6KL — Mechanical
ParameterValue
Mounting positionany
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SM3342-6KL — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM3342-6KL is a SENTRON 5SM3-series residual current circuit breaker (RCCB), 4-pole, Type A, rated 25 A at 400 V AC with a 30 mA trip threshold. It's an instantaneous (short-time-delay-free) device, meaning it trips on the residual current waveform without intentional delay — the go-to for general-purpose shock protection in TN and TT systems. Type A detection covers AC residual currents plus pulsating DC — the common waveform from single-phase rectifiers, variable-speed drives, and switching power supplies. If your downstream loads include electronics or motor drives, Type A is the correct choice over the simpler AC-only type. The 1 kA surge current resistance (I_{m}) covers the inrush from capacitive loads or nearby lightning-induced surges without nuisance tripping.

Mounts on DIN rail (REG profile) in any orientation — no top/bottom restriction on the supply side. Occupies 4 width units (72 mm wide) at a depth of 77 mm and height of 90 mm, with an installation depth of 70 mm behind the panel door. The N-left design means the neutral pole is on the left side of the device when viewed from the front; verify this matches your distribution board's busbar arrangement before wiring. Tightening torque is 2.5 to 3 N·m — use a torque screwdriver; under-torquing creates a high-resistance joint that can thermally damage the device over time. IP20 protection applies only when installed in a distribution board with conductors connected; the device itself is not sealed against dust ingress.

Environmental and lifecycle

Frequently asked questions

How do I get current pricing and availability for 5SM3342-6KL?

Pricing and stock levels are confirmed at quote time. Submit an RFQ through the storefront; the part is sourced to order through independent distribution channels.

What are the key ratings for 5SM3342-6KL?

4-pole Type A RCCB, 25 A rated current, 30 mA trip sensitivity, 400 V AC, 10 kA short-circuit current rating, DIN rail mount, N-left design.

What is the depth of the 5SM3342-6KL?

The overall depth is 77 mm, with an installation depth of 70 mm behind the panel door.

Will 5SM3342-6KL drop into a panel specified around 5SL4363-7?

No — the 5SL4363-7 is a Siemens 5SL series MCB (miniature circuit breaker), not an RCCB. They serve different protection functions (overcurrent vs. earth leakage) and are not direct replacements. The 5SM3342-6KL is an RCCB and requires a separate overcurrent protective device upstream.

MPN
5SM3342-6KL