Skip to main content
Siemens 5SM3344-6BA — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3344-6BA SENTRON RCCB, 4P, 40A, 30mA, Type A, 400

MPN5SM3344-6BA

Siemens SENTRON 5SM3 series, RCCB, 4-pole, Type A, In: 40 A, IΔn: 30 mA, Un: 400 V AC, 10 kA, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3344-6BA — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM3344-6BA — Identification
ParameterValue
Product designationRCCB
Product design / constructionInstantaneous
5SM3344-6BA — Mechanical
ParameterValue
Mounting positionany
Installation depth70 mm
5SM3344-6BA — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The 5SM3344-6BA: The 40 A rated current and 30 mA residual trip are the two numbers that decide the application: 40 A covers the main feed for a sub-distribution board or a heavy single load (e.g., a large pump or compressor), while 30 mA provides personal protection against direct contact — the standard threshold for socket-outlet circuits in most IEC-based codes. The Type A designation means it detects pulsating DC fault currents on top of sinusoidal AC, which is mandatory for circuits with single-phase rectifiers, variable-speed drives, or LED drivers that can generate smooth DC leakage.

Integration notes

Installation depth is 70 mm.

MPN
5SM3344-6BA