The Siemens 5SM3347-6KL is a SENTRON residual current operated circuit breaker (RCCB), 4-pole, Type A, rated 80 A at 400 V AC with a 30 mA trip sensitivity. It's an instantaneous design — no intentional delay — so it clears ground faults as fast as the waveform allows, which is what you want for personnel protection on a 50 Hz supply.
Panel integration
Snaps onto DIN rail (REG profile) in any mounting position. Depth is 77 mm, height 90 mm, width 72 mm (4 width units). Terminal capacity accepts 1.5 mm² minimum to 25 mm² maximum — solid or stranded. Supply can land top or bottom. The test button requires at least 100 V to operate, so you can functionally test it at line voltage.