Skip to main content
Siemens 5SM3444-0LB01 — Residual Current Breakers (RCCB/RCBO)

Siemens SENTRON 5SM3444-0LB01 RCCB, 4-pole, 40 A, 100 mA, 10

MPN5SM3444-0LB01

Siemens SENTRON 5SM3 series RCCB, 4-pole, type AC, short-time delayed, In: 40 A, IΔn: 100 mA, Un: 230 V AC, 10 kA SCCR, DIN rail mount, IP20.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3444-0LB01 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM3444-0LB01 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SM3444-0LB01 — Mechanical
ParameterValue
Mounting positionany
Maximum45 °C
Minimum-5 °C
Installation depth70 mm
5SM3444-0LB01 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens SENTRON 5SM3444-0LB01 is a 4-pole residual current operated circuit breaker (RCCB), type AC, short-time delayed, rated at 40 A and 100 mA tripping residual current on a 230 V AC supply. It carries a 10 kA short-circuit current rating and mounts on DIN rail (REG) — a standard fit for distribution boards in residential or light commercial panels.

The 100 mA residual-current trip threshold is set above the 30 mA level used for personal shock protection — this unit is sized for equipment protection or fire-prevention circuits where nuisance tripping from leakage on long cable runs or VFD filters would otherwise be a problem. The short-time delayed design means it withstands brief surge currents up to 3 kA without tripping, coordinating with downstream MCBs so only the faulted branch clears. The 4-pole construction switches all live conductors including the neutral — required for three-phase circuits where a neutral conductor is present.

Designed for DIN-rail (REG) mounting in SENTRON distribution boards. The top-or-bottom feed position simplifies panel wiring. Silicon-free construction suits environments where silicone outgassing can contaminate contacts or optics. Overvoltage category III means it is rated for fixed-installation mains supply — downstream of the service entrance but upstream of socket outlets.

Frequently asked questions

Where can I buy 5SM3444-0LB01 and how do I get a price?

The 5SM3444-0LB01 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is 5SM3444-0LB01's listed maximum ambient temperature?

The maximum ambient operating temperature is 45 °C; storage maximum is 75 °C.

What is 5SM3444-0LB01's listed minimum ambient temperature?

The minimum ambient operating temperature is -5 °C; storage minimum is -40 °C.

Will 5SM3444-0LB01 drop into a panel that was specified around 5SQ2670-2YA16 without rewiring?

No — the 5SQ2670-2YA16 is a 4-pole MCB (16 A, C-curve, 400 V AC, 55 mm depth) while the 5SM3444-0LB01 is a 4-pole RCCB (40 A, 100 mA, 230 V AC, 70 mm depth). They serve different protection functions and have different depth and voltage ratings; direct substitution is not possible without rewiring and re-evaluating the panel coordination.

MPN
5SM3444-0LB01