Siemens 5SM3614-8KL

Siemens 5SM3614-8KL SENTRON RCCB, 2-pole Type A Selective, 4

MPN 5SM3614-8KL

Siemens SENTRON 5SM3614-8KL RCCB, 2-pole, Type A selective, rated 40 A, 300 mA residual, 230 V AC, 50 Hz, 10 kA SCCR, DIN rail mount, N left.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

5SM3614-8KL specifications
ParameterValue
Short circuit rating10 kA
Poles2
MountingDIN rail (REG)
Temp operating max45 °C
Temp operating min-25 °C
Depth70 mm
Width36 mm
Height90 mm

Product details

The Siemens SENTRON 5SM3614-8KL is a 2-pole residual current operated circuit breaker (RCCB) rated 40 A at 230 V AC, 50 Hz, with a 300 mA Type A selective trip characteristic. The selective (S-type) design means it introduces a deliberate time delay on earth faults, allowing downstream RCCBs to clear first — critical for coordination in multi-level distribution boards where you want the faulted subcircuit to isolate without taking the whole board dark.

Mounts on DIN rail (REG) in any position, occupies 2 width units (36 mm), and accepts solid or stranded conductors from 1 to 16 mm² at the screw terminals (torque 2.5–3 N·m). IP20 with conductors connected and distribution board installed — standard for enclosed panel use.

MPN
5SM3614-8KL