It carries an 80 A rated current and trips at 300 mA residual current, with a rated supply voltage of 230 V AC. The instantaneous design means it responds to fault currents without intentional delay, making it suitable for general-purpose shock protection in residential and commercial distribution boards.
Mounts on DIN rail (REG) and occupies 2.5 width units (about 45 mm). Installation depth is 70 mm. The screw terminals accept solid or stranded conductors from 1.5 to 25 mm², with a tightening torque of 2.5 to 3 N·m.