Skip to main content
Siemens 5SM3642-4KK14 — Residual Current Breakers (RCCB/RCBO)

Siemens 5SM3642-4KK14 SENTRON RCCB, Type B+, 25 A, 4-Pole, 4

MPN5SM3642-4KK14

Siemens SENTRON 5SM3 series RCCB, 4-pole, Type B+ fault current, 25 A rated at 400 V AC, 10 kA SCCR, short-time delayed, DIN rail mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

5SM3642-4KK14 — Electrical Ratings
ParameterValue
Number of poles4
Overvoltage categoryIII
5SM3642-4KK14 — Identification
ParameterValue
Product designationRCCB
Product design / constructionShort-time delayed
5SM3642-4KK14 — Mechanical
ParameterValue
Mounting positionany
Width72 mm
Height90 mm
Depth77 mm
Installation depth70 mm
5SM3642-4KK14 — Environmental
ParameterValue
IP degree of protectionIP20, if the distribution board is installed, with connected conductors

Product details

The Siemens 5SM3642-4KK14 is a 4-pole residual current circuit breaker (RCCB) from the SENTRON 5SM3 series, designed for 400 V AC systems at 50/60 Hz. Rated at 25 A continuous with a 10 kA short-circuit current rating (SCCR), it's sized for sub-distribution boards feeding mixed loads. The short-time delayed design (S-type) provides selectivity with downstream RCCBs, so a fault on a branch trips the branch device rather than this main unit — keeps the rest of the board live.

The 25 A rating holds at 40 °C and 45 °C; derate to 24 A at 50 °C, 23 A at 55 °C, and 22 A at 60 °C, down to 20 A at 70 °C. If your enclosure runs warm, use the 50 °C column for sizing — a 25 A circuit on a hot panel floor may need the next frame up. That's standard for most commercial sub-distribution; verify against your transformer size and cable length if the available fault current exceeds 10 kA. Type B+ detection covers AC, pulsating DC, and smooth DC fault currents up to the rated residual current. The surge current resistance of 3 kA (8/20 µs waveform) means it won't nuisance-trip on lightning-induced surges common in industrial mains. The I²t rating of 70,000 A²s gives coordination data for upstream MCBs or fuses — useful when building a selective distribution board per IEC 60947-2.

Occupies 4 width units (72 mm wide, 90 mm tall, 77 mm deep with 70 mm installation depth). Mounting position is unrestricted — horizontal, vertical, or flat — which helps in tight enclosures.

Frequently asked questions

Where can I buy the 5SM3642-4KK14 and get a price?

This part is sourced and quoted to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing at the time of order.

What is the depth of the 5SM3642-4KK14?

The listed depth is 77 mm, with an installation depth of 70 mm into the distribution board.

What conductor sizes does the 5SM3642-4KK14 accept?

It accepts solid and stranded conductors from 1.5 mm² up to 25 mm².

Will the 5SM3642-4KK14 drop into a panel specified for the 5SY4304-7CV?

No — the 5SY4304-7CV is a miniature circuit breaker (MCB), not an RCCB. The 5SM3642-4KK14 is a 4-pole Type B+ RCCB with different function, wiring, and space requirements. They are not direct drop-in substitutes.

What compliance documentation does Siemens provide for the 5SM3642-4KK14?

The part carries overvoltage category III rating per IEC 60947-2 and is designed to DIN EN 61346-2 and DIN EN 81346-2 standards. It is finger and back-of-hand safe (IP20 when installed). For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration through the RFQ process.

MPN